Mercury Plant Controller Installation Guide
Probe Offsets
Each probe input, displayed as C-01 to C-08 from the controller display menu, can have an offset applied;
Up to ± 20
O
C in increments of 0.1
O
C.
Display Messages
The following messages can appear on the display during normal operation.
Pressure Transducer Fault
Compressor Fault
Compressor Run Fault
Configuration / Set up error
Discharge Pressure Trip alarm
Note 10: If Only 1 Transducer is fitted and the controller is set to a single section type, for example Pack, then
Display 1 will show the current suction pressure but Display 2 will show Ft. Transducer input 2 is on by default to
allow for the fitment of a transducer for monitoring purposes. If this probe is not fitted then set the parameter
“Trans2 Span” to 0. This will clear the fault alarm.
Network Alarms
The table below shows the text and associated type number that is sent to the system “front end”. The type number
is normally used to provide different alarm actions.